Metered Rack PDU

Metered rack PDUs with billing-grade +/-1% accuracy let colocation operators allocate real power spend per tenant.

Metering Classes and Accuracy

Rack PDU metering falls into three practical classes: basic strip, meter-at-inlet, and per-outlet metering. A billing-grade PDU measures current at every outlet and reports true RMS power with +/-1% accuracy, which is sufficient to allocate energy cost per tenant rather than estimate by nameplate.

Most metered PDUs from Shenzhen production lines use IEC C13 outlets rated at 10 A and C19 outlets at 16 A, with C21 for hot-condition circuits. When procurement specifies +/-1% accuracy on the datasheet, the PDU uses dedicated current transformers and calibration data, not simple shunt estimates.

Metered PDU Specification Reference

ParameterValue
Metering accuracy+/-1%, true RMS at outlet and phase level
Form factor0U vertical or 1U horizontal
Input voltage208 V or 400 V three-phase, 50/60 Hz
Outlet typesIEC C13 (10 A), C19 (16 A), C21 (16 A hot condition)
Rated load11-22 kW depending on inlet and outlet mix
MonitoringVoltage, current, power, power factor, energy per outlet
CommunicationsModbus TCP, SNMP, billing data export
CertificationsUL 62368-1
MOQ10-100 pcs
Lead time15-30 days from Shenzhen

Metered vs Switched vs Basic Rack PDU

FeatureBasicMeteredSwitched
Outlet-level current dataNoYes, +/-1% per outletYes, +/-1% per outlet
Remote outlet switchingNoNoYes
Billing-grade accuracyNoYesYes
Typical load rangeUp to 22 kW11-22 kW11-22 kW
Cost per outletLowestModerateHighest
Best fitFixed infrastructureColocation tenant billingRemote reboot and capacity management

Colocation Billing with 120 kW AI Cabinets

When AI racks cross 120 kW per cabinet, liquid cooling becomes mandatory and power density starts to resemble a small substation. For colocation operators, that concentration makes tenant-level billing accuracy a revenue issue rather than an instrumentation detail. A +/-1% metered PDU at each rack provides the audit trail needed to reconcile utility bills, cooling load, and tenant invoices.

At these densities, estimating consumption from server nameplates fails because GPU utilization varies minute to minute. Billing-grade PDU data lets you charge actual measured energy per tenant, set power caps, and identify under-utilized capacity. The same metering stream feeds the DCIM system for capacity planning and PUE calculations.

Get Metered PDU Pricing

Send your rack load profile and we will quote UL 62368-1 metered PDUs with +/-1% accuracy within 48 hours.

Request a Quote →

Input vs outlet metering

Input metering tells you the rack total; outlet metering tells you which tenant, which server, which circuit. For colocation billing you need both: input accuracy for utility reconciliation, outlet accuracy for the customer invoice. The two numbers should agree within 1 percent — a larger gap usually means a calibration or wiring issue, not a PDU fault.